ABK2027IQE01_A - Installation and Operation Manual
•
Auxiliary contacts.
•
Main shaft.
•
Mechanism.
To locate these components, see the AC thermomagnetic circuit breaker operation and maintenance manual.
The lubricant recommended by the manufacturer is PLG-322 by N.E.O. For equivalents, please contact Ingeteam.
Fuses (check, voltage-free)
Check the condition of the various fuses protecting the unit. Check for continuity via a suitable multimeter.
Below are the fuses that can be used with the units.
DCAC connections module
DC Power supply fuses
Common mode filter fuses (-CMC)
If one of the fuses is broken, replace it.
Thermomagnetic circuit breakers (check, voltage-free)
The thermomagnetic circuit breakers are the following:
•
Q1
•
Q2
•
Q4
Activate the thermomagnetic circuit breakers to check their proper performance.
If one of the thermomagnetic circuit breakers is broken, replace it.
Condenser capacity (check, voltage-free)
Check the BUS condenser capacity and the condenser of the harmonic filter.