ABK2027IQE01_A - Installation and Operation Manual
Phase connection via two terminals with one hole
A
B
D
C
C
B
E
≤
0.39 in
≤
1.3 in
M12
A. M12 DIN 933 screw.
B. M12 NFE-25 511 M washer.
C. Terminal. Hole diameter of M12, maximum thickness of 0.39 in (10 mm), maximum width of 1.3 in
(33 mm).
D. Busbar. When using a single hole terminal, use only the
top hole in the connection position of the plate.
E. M12 DIN 934 nut.
Phase connection via a terminal with two holes
A
B
D
C
B
E
13/4 in
≤
0.39 in
≤
1.3 in
M12
M12
A. M12 DIN 933 screw.
B. M12 NFE-25 511 M washer.
C. Terminal. Diameter of the M12 hole, maximum thickness of 0.39 in (10 mm), maximum width of 1.3 in
(33 mm), vertical distance between holes of 13/4 in (44.5 mm).
D. Busbar.
E. M12 DIN 934 nut.
113
AC connection
Ingeteam
Summary of Contents for INGECON SUN 1000TL U B360
Page 1: ...INGECON SUN PowerMax TL U B 1000 Vdc Installation and Operation Manual...
Page 22: ...ABK2027IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Page 176: ...Notes...
Page 177: ...Notes...
Page 178: ...Notes...
Page 180: ...ABK2027IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...