ABK2027IQE01_A - Installation and Operation Manual
Values and times of disconnection of the voltage and frequency protections in the interconnection of the unit with the electrical
company (for all equipment)
Levels
Simulated source
Maximum time (s) at 60 Hz before
the cessation of the current to the
simulated source
Voltage (V)
Frequency (Hz)
A
< 0.50 Vnom
Nominal
0.16
B
0.50 Vnom ≤ V < 0.88 Vnom (Adjustable,
0.88 Vnom as standard)
Nominal
0.16 ~ 2 (Adjustable, 2 as standard)
C
1.10 Vnom ≤ V < 1.20 Vnom (Adjustable,
1.10 Vnom as standard)
Nominal
0.16 ~ 1 (Adjustable, 1 as standard)
D
1.20 Vnom ≤ V
Nominal
0.16
E
Nominal
f > 60.5
0.16
F
Nominal
f < (59.8 ~ 57.0)
(Adjustable, 59 as standard)
0.16
G
Nominal
f < 57
0.16
Precision of the values and times of disconnection of the voltage and frequency protections
Voltage
± 1 %
Frequency
± 0.1 Hz
Time
0.06 s