ABK2027IQE01_A - Installation and Operation Manual
The normally closed, voltage-free contacts to monitor are installed between the two free positions on terminal
-X38.1, removing the vertical link.
-X38.1
•
Open contact: fault in the monitored component.
•
Closed contact: no fault at monitored component.
To make the connection, follow the following steps:
1. Strip the cables.
2. Crimp the wire ends according to the wire gauge being used.
3. Open the terminal. The terminals used in this terminal strip are of the clamp type. To insert the cable into
the desired position press with a flat head screwdriver, insert the cable and then remove the screwdriver.
100
Connection options
Ingeteam