ABK2027IQE01_A - Installation and Operation Manual
CAUTION
The maximum length permitted for the wiring of this contact is 10 meters. If necessary to use longer wiring, add
an intermediate relay as shown in the following figure.
ETAP
New relay
To make the connection, follow the following steps:
1. Strip the cables.
2. Crimp the wire ends according to the wire gauge being used.
3. Open the terminal. The terminals used in this terminal strip are of the clamp type. To insert the cable into
the desired position press with a flat head screwdriver, insert the cable and then remove the screwdriver.
4. Remove the vertical link.
102
Connection options
Ingeteam
Summary of Contents for INGECON SUN 1000TL U B360
Page 1: ...INGECON SUN PowerMax TL U B 1000 Vdc Installation and Operation Manual...
Page 22: ...ABK2027IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Page 176: ...Notes...
Page 177: ...Notes...
Page 178: ...Notes...
Page 180: ...ABK2027IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...