ABK2027IQE01_A - Installation and Operation Manual
•
The inverter busbars are made of copper. We recommend using tined copper terminals, while copper
terminals are allowed. If you use aluminum cables, you must use bimetallic terminals or other
components that eliminate the galvanic couple of the joint.
•
Use the screws, washers and nuts specified by Ingeteam.
•
All torques indicated must be respected and maintained.
Wire gauge
Tightening torque
Phases
Up to ten wires per phase, depending on the type of busbar
Minimum
In accordance with the current
circulating through the conductors
405 lb.in (45.7 Nm) (with lubrication)
Maximum
750 kcmil*
Neutral
Section
6 AWG
44 lb.in (5 Nm), M6 terminal (without
lubrication)
* To facilitate handling of the wiring, Ingeteam recommends using more than one smaller gauge cable instead of one large gauge
cable. For example, it is preferable to use two 400 kcmil cables instead of one 750 kcmil cable.
Phase connection via a terminal with one hole
A
B
D
C
B
E
≤
0.39 in
≤
1.3 in
M12
A. M12 DIN 933 screw.
B. M12 NFE-25 511 M washer.
C. Terminal. Hole diameter of M12, maximum thickness of 0.39 in (10 mm), maximum width of 1.3 in
(33 mm).
D. Busbar. When using a single hole terminal, use only the
top hole in the connection position of the plate.
E. M12 DIN 934 nut.
112
AC connection
Ingeteam
Summary of Contents for INGECON SUN 1000TL U B360
Page 1: ...INGECON SUN PowerMax TL U B 1000 Vdc Installation and Operation Manual...
Page 22: ...ABK2027IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Page 176: ...Notes...
Page 177: ...Notes...
Page 178: ...Notes...
Page 180: ...ABK2027IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...