To check the proper status of the BUS condenser, access it via the upper part of one of the power module and
measure the capacity with the proper multimeter between 1-2 of the following figure.
1
2
The measurement result must be the following:
Measurement points
Value
1-2
12000 ± 1200 μF
157
Maintenance