ABK2027IQE01_A - Installation and Operation Manual
1. Connect the grounded pole of each unit through a 35 mm
2
section cable with 1000/1500 V insulation.
This connection can be done through the cable grommets provided in the bases of the units in question.
Inverter 1
Inverter 2
2. Connect the CAN communication buses from both inverters using the cable provided. To connect the
communication buses, carry out the following process:
Inverter 1
CAN
Inverter 2
On the inverter where the grounding kit (-TSGND) is being installed, remove the end of line resistor
from the wiring between -X26.3D and -X26.4D and connect the CAN cable with the color code
described in the diagram to -X26.1C, -X26.2C, -X26.3C, -X26.4C.
76
Connection of the PV array grounding kit [optional]