ABK2027IQE01_A - Installation and Operation Manual
Siba
Fuse holder base
size
Fuse size
Rated current
Rated voltage
Without an indicator
With indicator
and adapter for
microswitch
20 028 28.50
20 028 29.50
2XL, 3L
NH1XL
50 A
1100 VDC
20 028 28.63
20 028 29.63
63 A
20 028 28.80
20 028 29.80
80 A
20 028 28,100
20 028 29,100
100 A
20 028 28,125
20 028 29,125
125 A
20 028 28,150
20 028 29,150
150 A
20 028 28,160
20 028 29,160
160 A
20 028 28,175
20 028 29,175
175 A
20 028 28,200
20 028 29,200
200 A
20 031 28,200
20 031 29,200
NH3L
200 A
20 031 28,250
20 031 29,250
250 A
20 031 28,315
20 031 29,315
315 A
20 031 28,350
20 031 29,350
350 A
20 031 28,400
20 031 29,400
400 A
Mersen
Fuse holder base size
Fuse size
Rated current
Rated voltage
HP12NH2XLGPV200
2XL, 3L
2
200 A
1000 VDC
HP12NH2XLGPV250
250 A
HP12NH3LGPV250
3L
3
250 A
HP12NH3LGPV350
350 A
HP12NH3LGPV400
400 A
6.8. Requirements for transformers
6.8.1. Grid connection transformer
CAUTION
These units must be connected to a transformer with the neutral of the low-voltage side isolated, thus
generating an IT grid.
This section lists the technical specifications of the grid connection transformer which converts the medium or
high supply voltage to the operating voltage of the unit.
1. The transformer’s power must be greater than the sum of the power ratings of the connected inverters,
keeping in mind the locations environmental conditions and height.
53
Preparation for installing the unit
Ingeteam
Summary of Contents for INGECON SUN 1000TL U B360
Page 1: ...INGECON SUN PowerMax TL U B 1000 Vdc Installation and Operation Manual...
Page 22: ...ABK2027IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Page 176: ...Notes...
Page 177: ...Notes...
Page 178: ...Notes...
Page 180: ...ABK2027IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...