ABK2027IQE01_A - Installation and Operation Manual
CAUTION
The distance between the inverter and the transformer must not be greater than 30 meters.
6.8.2. Auxiliary transformer
Some unit components such as fans, contactors or power supplies, require auxiliary power to operate. No electronic
equipment may be connected to the power grid. All auxiliary loads must be isolated from the power grid via a
galvanically isolated transformer.
This is why it is essential to install an auxiliary services transformer with galvanic isolation, suitable for the grid
with a single phase voltage of 220 V 50/60 Hz.
CAUTION
The Auxiliary service transformer must have galvanic insulation. It is forbidden to use autotransformers or other
devices without galvanic isolation to match the grid voltage to the single phase voltage required for the proper
operation of the unit.
Ingeteam accepts no liability for any consequences arising from non-compliance with these instructions.
It is possible to install the
auxiliary services kit
, and if you prefer you may install an auxiliary transformer acquired
from third parties. In this last example, you should follow the following guidelines.
The auxiliary transformer transforms the voltage from the power part of the unit to its control and current part.
L1
L2
L3
L1
L2
L3
I> I> I>
L1 L2 L3 N
Auxiliary consumptions
Auxiliary transformer
Residual current device
Circuit breaker (characteristic
L, I)
Medium voltage transformer
The primary circuit is connected to the power input. We recommend installing protection and switching
components to protect this transformer.
In the event of using a residual current device between the transformer secondary connected to ground and the
auxiliary loads of the unit, said device shall be 300 mA, of industrial use, a selective version and super immune.
55
Preparation for installing the unit
Ingeteam
Summary of Contents for INGECON SUN 1000TL U B360
Page 1: ...INGECON SUN PowerMax TL U B 1000 Vdc Installation and Operation Manual...
Page 22: ...ABK2027IQE01_A Installation and Operation Manual DC supply 22 Unit description Ingeteam...
Page 176: ...Notes...
Page 177: ...Notes...
Page 178: ...Notes...
Page 180: ...ABK2027IQE01_A 05 2019 Ingeteam Power Technology S A www ingeteam com...