3. Electrical Connections
3.14. Supply to electronics and blower
Supply voltage: 3 x AC 380...480V, 50...60 Hz
Connected load: 300 VA (for maximum utilization of supply to electronics)
The mains connections for the supply to power and electronics sections are
strapped when the unit is delivered. No additional mains connection is thus
required for the electronics section.
If a separate supply for the electronics is needed, e.g., to store the TVD's
diagnostic signals with mains disconnection, then the links between power
and electronics section can be removed. Short-circuit protection need only be
provided in the control cabinet for the connecting cable, e.g., miniature circut-
breaker 3 VU 1300 -.MF00, 0,6 ... 1A, Siemens. Tap off electronics power
source between commutation chock and TVD.
1) Drive module without blower connection
TDM ...-...-300-W0
TDM ...-...-300-W1-000
TDA, DDS 2.1-W..
2) Drive module with blower connection
TDM ...-...-300-W1-115
TDM ...-...-300-W1-220
KDA, KDS, KDF, TFM
socket
part no. 219 118
Fig. 3.13: Blower connections of the drive module
Electronics
1)
2)
2)
supply
module
Blower
Q1
L1
L2
L3
1U1
2U1
1V1
2V1
1W1
2W1
1L+
EPU+
2L+
EPU-
RB1
IB
RB2
EB
L1
DC bus
smoothing
reactor
X7
K2
F2
TVD/X7/2
Commutation choke KD .. or
choke integrated in the NAM
The TVD 1.3 needs no additional mains connection for the blower. If drive
modules are used that need a mains connection for cooling, this is done on the
drive module next to the TVD 1.3. The mains connector for the blower supply
must be ordered separately. The order number for the socket is 219 118.
Fig. 3.12: Terminal block X7 for separate supplies to power and electronics sections