2-19
Table 2.8 Continued
Cl
a
ss
ifi
-
ca
tion Symbol Name
Functions
[30A],
[30B],
[30C]
Alarm
relay
output
(for any
fault)
(1) Outputs a contact signal (SPDT) when a protective function has been
activated to stop the motor.
Contact rating: 250 VAC 0.3A cos
I
= 0.3
+48
VDC,
0.5A
(2) A command similar to terminal [Y1] can be selected for the transistor
output signal and use it for signal output.
(3) Switching of the normal/negative logic output is applicable to the fol-
lowing two contact outputs: "Terminals [30A] and [30C] are
short-circuited for ON signal output" or "the terminals [30B] and [30C]
are short-circuited (non-excite) for ON signal output."
C
o
m
m
u
ni
ca
tion
RS485
port*
RS485
communi-
cations I/O
(1) Used to connect the inverter with PC or PLC using RS485 port.
(2) Used to connect the inverter with the remote keypad. The inverter
supplies the power to the remote keypad through the extension cable
for remote keypad.
*
This terminal can be used with standard inverters equipped with an RS485 communications card (option).
-
Route the wiring of the control terminals as far from the wiring of the main circuit as
possible. Otherwise electric noise may cause malfunctions.
-
Fix the control circuit wires inside the inverter to keep them away from the live parts of
the main circuit (such as the terminal block of the main circuit).
2.3.8 Switching of SINK/SOURCE (Jumper Switch)
Before changing the jumper switch, wait for at least five minutes after the power has been turned
off, then check that the DC link circuit voltage between main circuit terminals P (+) and N (-) does
not exceed the safety voltage (+25 VDC) using a multimeter. An electric shock may result if this
warning is not heeded as there may be some residual electric charge in the DC bus capacitor
even after the power has been turned off.
Figure 2.17 Switching of SINK/SOURCE (Jumper Switch)
To switch the sink/source of the digital
input signal, change the position of the
jumper switch using a pair of long-nose
pliers, as shown in Figure 2.17.
At the factory setting, the jumper switch
is positioned at SOURCE.
Relay cont
act
o
u
tp
ut
Summary of Contents for Jaguar CUB
Page 47: ...3 5 Figure 3 2 Alarm Mode Status Transition...
Page 77: ...5 4...
Page 78: ...5 5 E codes Extension Terminal Functions...
Page 80: ...5 7...
Page 81: ...5 8 C codes Control Functions of Frequency...
Page 84: ...5 11 y codes Link Functions...
Page 149: ...8 5 8 3 Common Specifications...
Page 150: ...8 6...
Page 153: ...8 9 8 5 External Dimensions 8 5 1 Standard Models...
Page 154: ...8 10...
Page 155: ...8 11 8 5 2 Models Available on Order EMC Filter Built in Type...
Page 156: ...8 12...