2-14
Table 2.8 Symbols, Names and Functions of the Control Circuit Terminals
Cl
a
ss
ifi
-
ca
tion Symbol Name
Functions
[13] Potenti-
ometer
power
supply
Power supply (+10 VDC) for frequency command potentiometer (Potenti-
ometer: 1 to 5 k
:
)
Allowable output current: 10 mA
[12] Voltage
input
(1) The frequency is set according to the external analog input voltage.
0 to +10 (VDC)/0 to 100 (%) (Normal mode operation)
+10 to 0 (VDC)/0 to 100 (%) (Inverse mode operation)
(2) Used for reference signal (PID process command) or PID feedback
signal.
(3) Used as additional auxiliary setting for various main frequency com-
mands.
* Input impedance: 22 k
:
* Allowable maximum input voltage is +15 VDC. If the input voltage is +10
VDC or more, the inverter will limit it at +10 VDC.
[C1] Current
input
(1) The frequency is set according to the external analog input current
command.
+4 to +20 (mA DC)/0 to 100 (%) (Normal mode operation)
+20 to +4 (mA DC)/0 to 100 (%) (Inverse mode operation)
(2) Used for reference signal (PID process command) or PID feedback
signal.
(3) Connects PTC thermistor for motor protection.
(4) Used as additional auxiliary setting to various main frequency com-
mands.
* Input impedance: 250
:
* Maximum allowable input current is +30 mA DC. If the input current
e20 mA DC, the inverter will limit it at +20 mA DC.
A
n
al
og
in
pu
t
[11] Analog
common
Common terminal for analog input and output signals
This terminal is electrically isolated from terminals [CM] and [Y1E].
Summary of Contents for Jaguar CUB
Page 47: ...3 5 Figure 3 2 Alarm Mode Status Transition...
Page 77: ...5 4...
Page 78: ...5 5 E codes Extension Terminal Functions...
Page 80: ...5 7...
Page 81: ...5 8 C codes Control Functions of Frequency...
Page 84: ...5 11 y codes Link Functions...
Page 149: ...8 5 8 3 Common Specifications...
Page 150: ...8 6...
Page 153: ...8 9 8 5 External Dimensions 8 5 1 Standard Models...
Page 154: ...8 10...
Page 155: ...8 11 8 5 2 Models Available on Order EMC Filter Built in Type...
Page 156: ...8 12...