E 6
Operation protection
Problem
An error occurred due to incorrect operation of the motor.
Possible Causes
What to Check and Suggested Measures
(1) The key was pressed
when H96 = 1 or 3.
Î
Change the setting for H96 so that the STOP key priority
function is invalid to ensure that the inverter does not
operate unexpectedly.
(2) The start check function
was activated when H96 =
2 or 3.
Check that E 6 occurs when:
- The power is switched on
- An alarm is released (by pressing the
key or turning
reset alarm (RST) on)
- The link command (LE) has switched the inverter
operations.
Î
Reconsider the running sequence to avoid input of the run
command when
E 6
has occurred.
Î
Change the setting for H96 so that the STOP key priority
function is invalid to ensure the inverter does not operate
unexpectedly.
(To reset the alarm, turn the run command off.)
[ 16 ]
E 8
RS485 communications error
Problem
A communications error occurred during RS485 communications.
Possible Causes
What to Check and Suggested Measures
(1) Host controllers (e.g.,
PLCs and personal
computers) did not
operate due to incorrect
settings and/or defective
software/hardware.
Check the controllers.
Î
Remove the cause of the controller error.
(2) Relay converters (e.g.,
RS232C/RS485
converter) did not operate
due to incorrect
connections and settings,
and defective hardware.
Check the converter (e.g., check for poor contact).
Î
Change the various converter settings, reconnect the wires,
or replace hardware (such as recommended devices) as
appropriate.
(3) Broken communications
cable or poor contact.
Check continuity of the cable, contacts and connections.
Î
Replace the cable.
(4) Even though no response
error detection time (y08)
has been set,
communications did not
occur cyclically.
Check the host controllers.
Î
Change the settings of host controller software, or make the
no response error detection time invalid (y08=0).
(5) A high intensity noise was
given to the inverter.
Check if appropriate noise control measures have been
implemented (e.g., correct grounding and routing of control
and main circuit wires).
Î
Improve noise control.
Î
Improve measures against noise from host controllers.
Î
Replace the relay converter with a recommended insulated
converter.
Summary of Contents for Jaguar CUB
Page 47: ...3 5 Figure 3 2 Alarm Mode Status Transition...
Page 77: ...5 4...
Page 78: ...5 5 E codes Extension Terminal Functions...
Page 80: ...5 7...
Page 81: ...5 8 C codes Control Functions of Frequency...
Page 84: ...5 11 y codes Link Functions...
Page 149: ...8 5 8 3 Common Specifications...
Page 150: ...8 6...
Page 153: ...8 9 8 5 External Dimensions 8 5 1 Standard Models...
Page 154: ...8 10...
Page 155: ...8 11 8 5 2 Models Available on Order EMC Filter Built in Type...
Page 156: ...8 12...