5-43
Retry waiting time (H05)
Sets the waiting time for automatic exit from Alarm mode. Refer to the timing
scheme diagram below.
Operation timing chart
H07
Gradual Acceleration/Deceleration
Specifies the acceleration and deceleration patterns (output frequency patterns).
Linear acceleration/deceleration
The inverter runs the motor with the constant acceleration and deceleration.
S-curved acceleration/deceleration
To reduce the impact on the inverter-driven motor during acceleration/deceleration,
the inverter gradually accelerates/decelerates the motor in both the accelera-
tion/deceleration zones.
Curvilinear acceleration/deceleration
The inverter drives the motor to output maximum performance with a constant
loading rate as follows:
- In the zone under the base frequency, linear acceleration/deceleration of con-
stant torque output for the motor
- In the zone above the base frequency, speed two times the base frequency and
acceleration/deceleration half of the base frequency