5-14
F02
Running/Stopping and Rotational Direction
Selects a source issuing a run command--keypad or external control signal input.
- If F02 = 0, 2, or 3, the inverter can run the motor by the
and
keys on the
built-in keypad. The motor rotational direction can be specified in two ways, ei-
ther by control signal input (F02 = 0) or by use of prefixed forward or reverse
rotation (F02 = 2 or 3).
When F02 = 0, to specify the motor rotational direction by control signal input,
assign the commands (FWD) and (REV) to terminals [FWD] and [REV], respec-
tively. Turn on the (FWD) or (REV) for the forward or reverse direction, respec-
tively, and then press the
key to run the motor.
- If F02 = 1, the inverter can run the motor by control terminal inputs. To specify the
motor rotational direction, assign the commands (FWD) and (REV) to terminals
[FWD] and [REV], respectively. Turn on the (FWD) or (REV) for the forward or
reverse direction, respectively. If both of (FWD) and (REV) are turned on si-
multaneously, the inverter immediately decelerates to stop the motor.
The table below lists the operational relationship between function code F02
(Running/Stopping and Rotational Direction), the
key operation, and control
signal inputs to terminals [FWD] and [REV], which determines the rotational direc-
tion.
Control signal inputs to
terminals [FWD] and [REV]
Function
code F02:
Key on the
keypad
Function code E98
(FWD) command
Function code E99
(REV) command
Motor
rotational
direction
OFF OFF Stop
ON OFF
Forward
OFF ON
Reverse
key
ON ON
Stop
OFF OFF
ON OFF
OFF ON
0
key
ON ON
Stop
OFF OFF Stop
ON OFF
Forward
OFF ON
Reverse
1 Ignored.
ON ON
Stop
key
Forward
2
key
Ignored.
Stop
key
Reverse
3
key
Ignored.
Stop
Summary of Contents for Jaguar CUB
Page 47: ...3 5 Figure 3 2 Alarm Mode Status Transition...
Page 77: ...5 4...
Page 78: ...5 5 E codes Extension Terminal Functions...
Page 80: ...5 7...
Page 81: ...5 8 C codes Control Functions of Frequency...
Page 84: ...5 11 y codes Link Functions...
Page 149: ...8 5 8 3 Common Specifications...
Page 150: ...8 6...
Page 153: ...8 9 8 5 External Dimensions 8 5 1 Standard Models...
Page 154: ...8 10...
Page 155: ...8 11 8 5 2 Models Available on Order EMC Filter Built in Type...
Page 156: ...8 12...