3-17
Table 3.6 Drive Monitoring Display Items
LED
monitor
shows:
Contents Unit
Description
3_00
Output
frequency
Hz
Output frequency before slip compensation
3_01
Output
frequency
Hz
Output frequency after slip compensation
3_02
Output
current
A Output
current
3_03
Output
voltage
V Output
voltage
3_05
Set
frequency
Hz Set
frequency
3_06
Running
direction
N/A
Displays the running direction currently being outputted.
F: forward; R: reverse, – – – –: stop
3_07
Running
status
N/A
Displays the running status in hex. format. Refer to "
Displaying
running status
" on the next page.
3_09
Load shaft
speed
(line speed)
rpm
(m/min)
The unit for load shaft speed is rpm and that for line speed is
m/min.
Display value = (Output frequency Hz before slip compensation)
u
(Function code E50)
appears for 10000 (rpm or m/min) or more. When
appears, decrease function code E52 data so that the LED
monitor displays 9999 or below, referring to the above equation.
3_10
PID process
commands
N/A
These commands are displayed through the use of function
code E40 and E41 data (PID display coefficients A and B).
Display value = (PID process command)
u
(Factor A - B) + B
If PID control is disabled, "– – – –" appears.
3_11
PID feedback
amount
N/A
This value is displayed through the use of function code E40
data and function code E41 data (PID display coefficients A and
B).
Display value = (PID feedback amount)
u
(PID display coefficient
A - B) + B
If PID control is disabled, "– – – –" appears.
Summary of Contents for Jaguar CUB
Page 47: ...3 5 Figure 3 2 Alarm Mode Status Transition...
Page 77: ...5 4...
Page 78: ...5 5 E codes Extension Terminal Functions...
Page 80: ...5 7...
Page 81: ...5 8 C codes Control Functions of Frequency...
Page 84: ...5 11 y codes Link Functions...
Page 149: ...8 5 8 3 Common Specifications...
Page 150: ...8 6...
Page 153: ...8 9 8 5 External Dimensions 8 5 1 Standard Models...
Page 154: ...8 10...
Page 155: ...8 11 8 5 2 Models Available on Order EMC Filter Built in Type...
Page 156: ...8 12...