5-12
* The table below lists the factory settings of "standard torque boost," "Nominal rated current of
standard motor," and "Nominal rated capacity of standard motor" in the "Default setting" column of
the above tables.
Table 5.1 Standard Motor Parameters
Standard value
torque boost (%)
Nominal rated current of
standard motor (A)
Nominal rated
capacity of standard
motor (kW)
Power supply
voltage
Applicable
motor
rating
(kW)
Function code F09
Function codes F11, E34 and P03
Function code P02
0.4 7.1
2.30
0.4
0.75 6.8
3.60
0.75
1.5 6.8
6.10
1.5
Three-phase
200 V
Single-phase
200 V
2.2 6.8
9.20
2.2
Three-phase
200 V
4.0 5.5
15.00
3.7
0.4 7.1
1.15
0.4
0.75 6.8
1.80
0.75
1.5 6.8
3.05
1.5
2.2 6.8
4.60
2.2
Three-phase
400 V
4.0
5.5
7.50
4.0
Note: When setting data to F11, E34 and P03, check the nameplate of the motor.