2-16
Item Min.
Max.
ON level
0V
2V
Operation
voltage
(SINK)
OFF level
22V
27V
ON level
22V
27V
Operation
voltage
(SOURCE) OFF level
0V
2V
Operation current at ON
(Input Voltage at 0 V)
2.5mA 5mA
Allowable leakage
current at OFF
- 0.5mA
Table 2.8 Continued
Cl
a
ss
ifi
-
ca
tion Symbol Name
Functions
[X1] Digital
input 1
[X2] Digital
input 2
[X3] Digital
input 3
[FWD] Forward
operation
command
[REV] Reverse
operation
command
(1) The various signals such as coast-to-stop, alarm from external equip-
ment, and multistep frequency selection can be assigned to terminals
[X1] to [X3], [FWD] and [REV] by setting function codes E01 to E03, E98,
and E99. For details, refer to Chapter 5, Section 5.2 "Overview of
Function Codes."
(2) Input mode, i.e. Sink/Source, is changeable by using the internal jumper
switch.
(3) Switches the logic value (1/0) for ON/OFF of the terminals between [X1]
to [X3], [FWD] or [REV], and [CM]. If the logic value for ON between [X1]
and [CM] is 1 in the normal logic system, for example, OFF is 1 in the
negative logic system and vice versa.
(4) The negative logic signaling cannot be applicable to [FWD] and [REV].
Digital input circuit specifications
[PLC] PLC
signal
power
Connects to PLC output signal power supply. (Rated voltage: +24 VDC,
Maximum output current: 50 mA)
Di
g
ita
l i
n
p
u
t
[CM] Digital
common
Common terminal for digital input signals
This terminal is electrically isolated from terminals [11] and [Y1E].
Summary of Contents for Jaguar CUB
Page 47: ...3 5 Figure 3 2 Alarm Mode Status Transition...
Page 77: ...5 4...
Page 78: ...5 5 E codes Extension Terminal Functions...
Page 80: ...5 7...
Page 81: ...5 8 C codes Control Functions of Frequency...
Page 84: ...5 11 y codes Link Functions...
Page 149: ...8 5 8 3 Common Specifications...
Page 150: ...8 6...
Page 153: ...8 9 8 5 External Dimensions 8 5 1 Standard Models...
Page 154: ...8 10...
Page 155: ...8 11 8 5 2 Models Available on Order EMC Filter Built in Type...
Page 156: ...8 12...