viii
Conformity to UL standards and Canadian standards (cUL certification)
If installed according to the guidelines given below, inverters marked with UL/cUL are considered as
compliant with the UL and CSA (cUL certified) standards.
1. Solid state motor overload protection (motor protection by electronic thermal overload relay)
is provided in each model.
Use function codes F10 to F12 to set the protection level.
2. Connect the power supply satisfying the characteristics shown in the table below as an
input power supply of the inverter.(Short circuit rating)
3. Use 75
q
C Cu wire only.
4. Use Class 1 wire only for control circuits.
5. Field wiring connection must be made by a UL Listed and CSA Certified closed-loop
terminal connector sized for the wire gauge involved. Connector must be fixed using the
crimp tool specified by the connector manufacturer.
Short circuit rating
Suitable for use on a circuit capable of delivering not more than B rms symmetrical amperes, A
volts maximum.
Power
supply
voltage
Inverter type
Power supply max. voltage A
Power supply current
㧮
CUB3A-2
CUB5A-2
CUB8A-2
CUB11A-2
T
h
ree-
pha
se 200
V
CUB17A-2
240 VAC
100,000 A or less
CUB1A5-4
CUB2A5-4
CUB3A7-4
CUB5A5-4
Thre
e-
p
hase
40
0V
CUB9A-4
480 VA
100,000 A or less
CUB3A-1
CUB5A-1
CUB8A-1
Sing
le
-
ph
a
se
20
0V
CUB11A-2
240 VAC
100,000 A or less
Notes 1) A box (
) in the above table replaces E suffix for filtered version
Summary of Contents for Jaguar CUB
Page 47: ...3 5 Figure 3 2 Alarm Mode Status Transition...
Page 77: ...5 4...
Page 78: ...5 5 E codes Extension Terminal Functions...
Page 80: ...5 7...
Page 81: ...5 8 C codes Control Functions of Frequency...
Page 84: ...5 11 y codes Link Functions...
Page 149: ...8 5 8 3 Common Specifications...
Page 150: ...8 6...
Page 153: ...8 9 8 5 External Dimensions 8 5 1 Standard Models...
Page 154: ...8 10...
Page 155: ...8 11 8 5 2 Models Available on Order EMC Filter Built in Type...
Page 156: ...8 12...