3-25
3.9 Reading Alarm Information--"Alarm information"
Menu #6 "Alarm information" in Programming mode shows the cause of the past 4 alarms as alarm
codes. Further, it is also possible to display alarm information that indicates the status of the inverter
when the alarm occurred. Figure 3.10 shows the status transition of the alarm information and Table
3.14 lists the contents of the alarm information.
If you cannot switch the menu to any other one, set function code E52 data to 2 (Full-menu mode).
Figure 3.10 "Alarm Information" Status Transition
Basic key operations
(1) With the menu displayed, use the
and
keys to select "Alarm information" (
6.AL
).
(2) Press the key to display the alarm list code (e.g.
1.OL1
).
In the list of alarm codes, the alarm information for last 4 alarms will be saved as an alarm
history.
(3) Each time the and
keys are pressed, the last four alarms are displayed in order from the
most recent one as "
1
", "
2
", "
3
" and "
4.
"
(4) Press the key while the alarm code is displayed, and the corresponding alarm item number
(e.g.
6_00
) and data (e.g. Output frequency) are displayed continuously in turn for 1 second
each. It is possible to display the item number (e.g.
6_01
) and data (e.g. Output current) for
each desired alarm using the
and
keys.
(5) Press the key to return to the alarm list. Press the
key again to return to the menu.
Summary of Contents for Jaguar CUB
Page 47: ...3 5 Figure 3 2 Alarm Mode Status Transition...
Page 77: ...5 4...
Page 78: ...5 5 E codes Extension Terminal Functions...
Page 80: ...5 7...
Page 81: ...5 8 C codes Control Functions of Frequency...
Page 84: ...5 11 y codes Link Functions...
Page 149: ...8 5 8 3 Common Specifications...
Page 150: ...8 6...
Page 153: ...8 9 8 5 External Dimensions 8 5 1 Standard Models...
Page 154: ...8 10...
Page 155: ...8 11 8 5 2 Models Available on Order EMC Filter Built in Type...
Page 156: ...8 12...