Programming Manual
ecomatmobile
CabinetController (CR0301) Runtime System V05
2016-04-21
ifm function elements
ifm function elements for the device CR0301
>
Parameters of the inputs
20971
Parameter
Data type
Description
INIT
BOOL
FALSE
TRUE (edge):
unit is initialised
FALSE:
during further processing of the program
FREQUENCY
WORD
PWM frequency in [Hz]
allowed = 20...250 = 0x0014...0x00FA
CHANNEL
BYTE
Number of the PWM output channel
0...3 for the outputs OUT00...OUT03
VALUE
BYTE
current PWM value
CHANGE
BOOL
TRUE:
Adopting new value from ...
• VALUE: after the current PMW period
• DITHER_VALUE: after the current Dither period
FALSE:
the changed PWM value has no influence on the output
DITHER_VALUE
BYTE
peak-to-peak value of the dither in [%]
permissible values = 0...100 = 0x00...0x64
DITHER_FREQUENCY
WORD
dither frequency in [Hz]
value range = 0...FREQUENCY / 2
FREQUENCY / DITHER_FREQUENCY must be even-numbered!
The FB increases all other values to the next matching value.