WindO/I-NV4 User’s Manual
30-23
3 Analog I/O Modules
30
Ex
pa
ns
io
n M
od
ule
s
■
Data Type
The analog output value can be handled as the set data type. There are two data types for the analog outputs.
YES: Supported, NO: Not supported
■
Min., Max.
The value written to the data register is output from the analog output. The values of
Min.
and
Max.
that can be
written are determined by the set
Signal Type
and
Data Type
. A parameter setting error occurs when a value is set
that exceeds the value of
Min.
or
Max.
.
The minimum and maximum values that correspond to the signal types and data types are as follows.
■
Data
The analog output data for the analog output set with the
Signal Type
, the
Data Type
, the
Min
. and the
Max
. is
stored in the data registers in the END progressing of each scan. The actual analog output data is not guaranteed
when the analog output
Status
is a value other than "0". However, 0V is output when
Signal Type
is set to
-10 to
+10V DC
.
■
Status
The status of the analog output
Data
is stored in data registers.
*1
Min.
and
Max.
can be set only when
Data Type
is set to
Optional range
. Set the values of
Min.
and
Max.
between -
32,768 and 32,767.
Data Type
FC6A-K2A1
FC6A-K2A4
FC6A-K4A1
FC6A-K4A4
FC6A-L06A1
FC6A-L06A4
FC6A-L03CN1
FC6A-L03CN4
Binary data
YES
YES
YES
YES
Optional range
YES
YES
YES
YES
Signal Type
Data Type
Binary data
Optional range
0 to 10V DC
0 to 4,095
-32,768 to 32,767
-10 to +10V DC
-2,048 to 2,047
-32,768 to 32,767
0 to 20mA DC
0 to 4,095
-32,768 to 32,767
4 to 20mA DC
0 to 4,095
-32,768 to 32,767
Status
Description
0
Operating normally
1
Reserved
2
Initializing
3
Parameter setting error
4
Hardware fault (external power supply error)
5 to 65,535
Reserved
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...