Settings
Device tab
1. Select instruction
This item selects the ZRN instruction to use from ZRN1 or ZRN2.
The output differs by the instruction.
2. S1 (source 1): Control register
S1 specifies the starting number of the data registers to use with the ZRN1 or ZRN2 instruction.
Starting from the specified number, 3 continuous words of data registers are used.
The range of available data register numbers is D0 to D997 and D1000 to D1997.
3. S2 (source 2): Initialization input
S2 specifies the initialization input. When the initialization input S2 is turned on, the initial values configured in the WindLDR ZRN
instruction dialog box, on the
Setting
tab, are stored in the control registers. An external input (I0 to I35) (Note) or an internal
relay (M0 to M1277) can be specified.
When the initialization input is on, the initial values are written to the data registers with each scan. To only initialize the values
one time, use the initialization input in combination with the SOTU (single output up) instruction or the SOTD (single output
down) instruction.
Note:
For the 40-I/O type, external inputs (I0 to I27) can be used.
1.
2.
3.
4.
5.
Instruction
Pulse output
ZRN1
Q14
ZRN2
Q15
Storage
destination
Function
Setting
Reference
Starting 0
Initial pulse frequency
0: 1 to 10,000 (increments of 1 Hz)
1: 20 to 10,000 (increments of 10 Hz)
"7. Initial pulse frequency" on page
19-28
Starting 1
Creep pulse frequency
0: 1 to 10,000 (increments of 1 Hz)
1: 20 to 10,000 (increments of 10 Hz)
"9. Creep pulse frequency" on page
19-29
Starting 2
Error status
0/2
Summary of Contents for microsmart pentra
Page 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Page 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...