ARAMP1 instruction (single-pulse output reversible control enabled) timing chart
[ARAMP1 instruction, S1 is specified as data register D200, S2 is specified as internal relay M0, S3 is disabled, D1 is specified as
data register D0, D2 is specified as internal relay M50]
When the ARAMP instruction input changes from off to on, pulses are output from Q14 according to the settings configured by the
data registers. The reversible control signal is output from Q16 or Q12. When pulse output starts, M50 turns on. M52 turns on
while the pulse frequency is increasing or decreasing. The pulses increase and decrease according to the frequency change time
until they reach the steady pulse frequency from the current pulse frequency. When the configured number of pulses are output,
the pulses stop. In this situation, M50 turns off and M51 turns on.
If the ARAMP instruction input turns off during pulse output, pulse output ends. If this input turns on again, the operation starts
from the beginning. Even if the contents of the data registers are changed during pulse output, the change is not reflected in the
pulse output operation. The changed content is reflected the next time the ARAMP instruction is started.
Forward and reverse cannot be changed until the pulse output pulse frequency is set to its minimum. In mode 1 for example,
forward and reverse cannot be changed until the pulse frequency is set to 200 Hz.
The changes from the initialization input are not reflected while the ARAMP1 instruction input is on. If you wish to initialize the
data registers with the initialization input, turn the initialization input on after turning off the input.
ARAMP instruction input
Output pulse
Q14
Pulse output ON
M50
Pulse output complete
M51
Pulse output status
M52
Control direction
0 (Forward)
1 (Reverse)
Reversible control
signal
Q16 (40-I/O type)
Q12 (48-I/O type)
S3
S2
M0
ARAMP
1
S1
D200
ARAMP instruction
input
D2
M50
D1
D0
Summary of Contents for microsmart pentra
Page 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Page 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...