5. D1 (destination 1): Monitor register
D1 specifies the starting number of the data registers to use with ARAMP1 or ARAMP2. Starting from the specified number, 9
continuous words of data registers are used. The range of available data register numbers is D0 to D991 and D1000 to D1991.
The contents of the monitor registers are read-only.
Note:
The upper and lower data registers change according to the 32-bit data storage method specified.
For details, see Chapter 5 "Special Functions" – "32-bit Data Storage Setting" in the FT1A Series SmartAxis Pro/Lite User's Manual.
Next step
This register stores the number of the step to execute next.
If the next step is 0, pulse output ends after the currently executed step is complete.
Running step
This register stores the number of the step that is currently being executed.
Steady pulse frequency monitor
This register stores the steady pulse frequency for the step that is currently being executed.
Frequency change time monitor
This register stores the frequency change time for the step that is currently being executed.
Set the time between 10 and 10,000 ms in increments of 10 ms. The first digit of the setting is discarded.
Preset value monitor
This register stores the preset value for the step that is currently being executed.
Current value
This register stores the number of pulses that have been output for the step that is currently being executed. The current
value is updated when the ARAMP instruction is executed at each scan.
Error status
If a configuration error occurs when a step starts executing, M8004 (user program execution error) is turned on and this
register is set to the error code.
Address
Description
Value range (unit)
Starting 0
Next step number
0 to 18
Starting 1
Running step number
1 to 18
Starting 2
Steady pulse frequency monitor
Mode 0: 1 to 10,000 (increments of 1 Hz), mode 1: 20 to 10,000
(increments of 10 Hz)
Starting 3
Frequency change time
monitor
10 to 10,000 ms
Starting 4
Preset value
monitor
(High word) (Note)
No pulse restriction: 0
Pulse restricted: 1 to 100,000,000 pulses
Starting 5
(Low word) (Note)
Starting 6
Current value
(High word) (Note)
1 to 100,000,000 pulses
Starting 7
(Low word) (Note)
Starting 8
Error status
0 to 9
Error code
Status
Description
0
Normal
—
3
Preset value designation error
The preset value was not set between 1 to 100,000,000.
4
Steady pulse frequency designation
error
The frequency was not set between 1 to 10,000 in operation mode 0. The
frequency was not set between 20 to 10,000 in operation mode 1.
5
Frequency change time designation
error
The frequency change time was not set between 10 and 10,000.
7
Step options designation error
The step options were not set to a valid value.
8
Next step number destination error
The next step number was not set between 0 and 18.
9
Interrupt number destination error
The interrupt number was not set between 1 and 18.
Summary of Contents for microsmart pentra
Page 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Page 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...