IBMV (Indirect Bit Move)
Applicable CPU Modules
Valid Devices
For the valid device address range, see pages 6-1 and 6-2
(Basic Vol.).
Internal relays M0 through M1277 can be designated as D1. Special internal relays cannot be designated as D1.
When T (timer) or C (counter) is used as S2 or D2, the timer/counter current value (TC or CC) is read out.
Make sure that the last source data determined by S1+S2 and the last destination data determined by D1+D2 are within the valid device range. If
the derived source or destination device is out of the valid device range, a user program execution error will result, turning on special internal relay
M8004 and ERR LED on the CPU module. For user program execution errors, see Chapter 4 “User Program Execution Errors” on page 4-21.
Either source device S2 or destination device D2 does not have to be designated. If S2 or D2 is not designated, the source or destination device is
determined by S1 or D1 without offset.
Examples: IBMV
Source device S1 and destination device D1 determine the type of device. Source device S2 and destination device D2 are the offset values to
determine the source and destination devices.
As a result, when input I0 is on, the ON/OFF status of internal relay M15 is moved to output Q14.
S1 + S2
D1 + D2
When input is on, the values contained in devices designated by S1
and S2 are added to determine the source of data. The 1-bit data so
determined is moved to destination, which is determined by the sum
of values contained in devices designated by D1 and D2.
IBMV
S1(R)
*****
S2
*****
D1(R)
*****
D2
*****
REP
**
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
S1 (Source 1)
Base address to move from
X
X
X
X
—
—
X
0 or 1
1-99
S2 (Source 2)
Offset for S1
X
X
X
X
X
X
X
0-65535
—
D1 (Destination 1)
Base address to move to
—
X
X
—
—
X
—
1-99
D2 (Destination 2)
Offset for D1
X
X
X
X
X
X
X
0-65535
—
M10
D10
Q0 + C5
S1 –
M10
I0
IBMV
S2
D10
D1 –
Q0
SOTU
REP
D2
C5
If the value of data register D10 designated by source device S2 is 5, the
source data is determined by adding the offset to internal relay M10
designated by source device S1.
If the current value of counter C5 designated by destination device D2 is 12,
the destination is determined by adding the offset to output Q0 designated
by destination device D1.
M27
M10
M17
M20
M15
5th from M10
Q17
Q0
Q7
Q10
12th from Q0
Q14
Summary of Contents for microsmart pentra
Page 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Page 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...