Changing, Confirming, and Clearing Preset Values for Timers and Counters
Preset values for timers and counters can be changed by selecting
Online
>
Monitor
>
Monitor
, followed by
Online
>
Custom
>
New Custom Monitor
on WindLDR for transferring a new value to the SmartAxis CPU module RAM as described on preceding
pages. After changing the preset values temporarily, the changes can be written to the user program in the SmartAxis CPU module
ROM or cleared from the RAM.
When the power is off, the temporarily changed preset values in the RAM are cleared and the original preset values are loaded.
Confirm the changed preset values to store them in the ROM. The timer/counter preset values can be confirmed only when
SmartAxis CPU module is stopped.
To access the PLC Status dialog box from the WindLDR menu bar, select
Online
>
Monitor
>
Monitor
, then
Online
>
Status
.
Confirm Button
After pressing the Clear or
Confirm button, the display
changes to “Unchanged.”
Clear Button
Data movement when changing a timer/counter preset value
When changing a timer/counter preset value using
Custom Monitor on WindLDR, the new preset value is
written to the SmartAxis CPU module RAM. The user
program and preset values in the ROM are not
changed.
Note:
The LCD and push buttons can also be used to
change preset values and confirm changed preset values.
See pages 5-63 and 5-65.
Data movement when confirming changed preset values
When the Confirm button is pressed before pressing
the Clear button, the changed timer/counter preset
values in the SmartAxis CPU module RAM are written
to the ROM.
When uploading the user program after confirming,
the user program with changed preset values is
uploaded from the SmartAxis CPU module ROM to
WindLDR.
Data movement when clearing changed preset values to restore original values
Changing preset values for timers and counters in the
SmartAxis CPU module RAM does not automatically
update preset values in the user memory, ROM. This
is useful for restoring original preset values. When
the Clear button is pressed before pressing the
Confirm button, the changed timer/counter preset
values are cleared from the RAM and the original
preset values are loaded from the ROM to the RAM.
WindLDR
SmartAxis CPU Module
User Program
ROM
RAM
User Program
Custom Monitor
New Preset Value
WindLDR
SmartAxis CPU Module
Confirm
User Program
ROM
RAM
User Program
Changed
Preset
Values
WindLDR
SmartAxis CPU Module
Clear
User Program
ROM
RAM
User Program
Original
Preset
Values
Summary of Contents for microsmart pentra
Page 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Page 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...