19: P
ULSE
O
UTPUT
I
NSTRUCTIONS
19-34
FT1A S
MART
A
XIS
U
SER
’
S
M
ANUAL
FT9Y-B1382
Settings
Device tab
1. Select instruction
This item selects the ARAMP instruction to use from ARAMP1 or ARAMP2.
The reversible control mode that can be selected varies based on the instruction.
For limitations due to the combination of instruction, reversible control mode, and the pulse output mode, see "8. Reversible
control enable" on page 19-38.
2. S1 (source 1): Control register
S1 specifies the starting number of the data registers to use with the ARAMP1 or ARAMP2 instruction.
Starting from the specified data register, "2+6 x N (N: number of steps)" continuous words of data registers are used.
The range of available data register numbers is D0 to D992 (dependent on the number of steps).
The steps operate with the settings that are configured when the steps start. If the settings for a step are changed after it starts
running, those changes are not reflected while the step is running.
Note:
The upper and lower data registers change according to the 32-bit data storage method specified.
For details, see Chapter 5 "Special Functions" – "32-bit Data Storage Setting" in the FT1A Series SmartAxis Pro/Lite User's Manual.
Storage destination
Function
Setting
Reference
Starting 0
Interrupt number
1 to 18
"11. Interrupt number" on
page 19-38
Starting 1
Reserved
Step 1 (6 words)
Starting 2
Steady pulse frequency
Mode 0: 1 to 10,000 (increments of 1 Hz)
Mode 1: 20 to 10,000 (increments of 10 Hz)
"13. Steady pulse
frequency" on page 19-39
Starting 3
Frequency change time
10 to 10,000 ms
"14. Frequency change
time" on page 19-39
Starting 4
Preset value (high word) (Note)
1 to 100,000,000 pulses
"15. Preset value" on page
19-39
Starting 5
Preset value (low word) (Note)
Starting 6
Step options
0 to 3
"16. Step options" on page
19-39
Starting 7
Next step number
1 to 18
"17. Next step number" on
page 19-39
2.
3.
5.
4.
6.
1.
Summary of Contents for microsmart pentra
Page 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Page 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...