19: P
ULSE
O
UTPUT
I
NSTRUCTIONS
19-2
FT1A S
MART
A
XIS
U
SER
’
S
M
ANUAL
FT9Y-B1382
Settings
Device tab
1. Select instruction
This item selects the PULS instruction to use from PULS1, PULS2, PULS3, or PULS4.
The pulse output, configurable operation modes, and enabling/disabling pulse counting varies based on the instruction.
2. S1 (source 1): Control register
S1 specifies the starting number for the data registers to use with the PULS1, PULS2, PULS3, or PULS4 instruction.
Starting from the specified number, 7 continuous words of data registers are used.
The range of available data register numbers is D0 to D993 and D1000 to D1993.
Note:
The upper and lower data registers change according to the 32-bit data storage method specified.
For details, see Chapter 5 "Special Functions" – "32-bit Data Storage Setting" in the FT1A Series Pro/Lite User's Manual.
1.
2.
3.
4.
Instruction
Pulse output
Configurable operation mode
Enable/disable pulse counting
PULS1
Q14
Operation mode 0: 1 Hz to 10 kHz
Operation mode 1: 200 Hz to 100 kHz
Pulse counting can be enabled or disabled
(Pulse counting range: 1 to 100,000,000)
PULS2
Q15
PULS3
Q16
Operation mode 0: 1 Hz to 5 kHz
Disable pulse counting
PULS4
Q17
Storage
destination
Function
Setting
Reference
Starting 0
Output pulse
frequency
PULS1,
PULS2
Mode 0: 1 to 10,000 (increments of 1 Hz)
Mode 1: 20 to 10,000 (increments of 10 Hz)
"6. Output pulse frequency" on
page 19-3
PULS3,
PULS4
Mode 0: 1 to 5,000 (increments of 1 Hz)
Mode 1: Cannot be specified
Starting 1
Reserved
—
—
Starting 2
Preset value
(high word) (Note)
1 to 100,000,000 pulses
"8. Preset value" on page 19-4
Starting 3
Preset value
(low word) (Note)
Starting 4
Current value
(high word) (Note)
1 to 100,000,000 pulses
"9. Current value" on page 19-4
Starting 5
Current value
(low word) (Note)
Starting 6
Error status
0 to 4
Summary of Contents for microsmart pentra
Page 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Page 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...