Examples: RAMP
RAMP1 instruction (reversible control disabled) timing chart
[RAMP1 instruction, S1 is specified as D200, D1 is specified as internal relay M50]
When the RAMP instruction input is on, pulses are output according to the settings configured by the control registers. M50 turns
on during pulse output. M52 turns on or off while increasing or decreasing the pulse frequency. Pulses are output so that the
frequency reaches the steady pulse frequency from the initial pulse frequency in the frequency change time. The frequency
increases or decreases every 10 ms. Pulse output stops when the pulses configured by the preset value are output. At this time,
M50 turns off and M51 turns on.
If the RAMP instruction input turns off during pulse output, pulse output is canceled. If the RAMP instruction input turns on again,
the pulse count is reset and pulse counting starts. Even if the contents of the control registers are changed during pulse output,
the change is not reflected in the operation of pulse output. The changed content is reflected the next time the RAMP instruction
is executed.
The changes from the initialization input are not reflected while the RAMP1 instruction input is on. If you wish to initialize the data
registers with the initialization input, turn the initialization input on after turning off the input.
D1
M50
S2
M0
RAMP
1
S1
D200
PAMP instruction
input
RAMP instruction input
Pulse output port
Q14
Pulse output ON
M50
Pulse output complete
M51
Pulse output status
M52
Summary of Contents for microsmart pentra
Page 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Page 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...