ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
89
Figure7-20 :
XV-Board DO attribute setting page
The settings are as follow:
Nickname
:
For user to define nicknames for each I/O channel,
this nickname will be displayed on the “I/O Information” and
“Rule Setting” pages.
Power On Value: Specify the initial status to be “ON” or to be
“OFF” when PMC-523x power on. Select the value from the
dropdown list of “Power On Value” field. The default value is
“OFF”.
PMC-523x provides 3 advanced functions, select the function
from the dropdown list:
Pulse Output: If the Pulse Output is selected, it will allow this
DO channel to perform pulse output and form a periodic
pulse cycle. In Pulse Output mode, the selected DO channel
will generate a square wave according to specified parameters
(Pulse High and Pulse Low). Pulse High indicates the “ON”
time duration and Pulse Low indicates the “OFF” time
duration in a periodic Pulse cycle. The unit is 100ms.
Auto OFF: When “Auto OFF” is selected, it allows this DO
channel to enable Auto OFF function. It is required to set up a
time interval, when this DO channel is set to be “ON” and the
duration of the ON status reaches the pre-set time interval ,
the DO will automatically be set to OFF. The unit is second.
Summary of Contents for PMC-523 Series
Page 1: ...ICP DAS PMC 523x PMC 224x PMD Power Meter Concentrator Series User Manual Version 3 2 4...
Page 165: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 150 Figure9 14 The Import of MQTT Topic...
Page 205: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 190 Figure10 53 PUE Setting Page 2...