ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
268
(Daily)
Max. Demand
(Monthly)
SA + 300128
2
Float
Floating Point
Daily Accumulated
Electricity
SA + 300130
2
Float
Floating Point
Monthly
Accumulated
Electricity
SA + 300132
2
Float
Floating Point
Yearly
Accumulated
Electricity
SA + 300134
2
Float
Floating Point
[3x] Input Register, Unit : Register(16 Bits)
VTHD
SA + 300136
2
Float
Floating Point
ITHD
SA + 300138
2
Float
Floating Point
Frequency Phase A
SA + 300140
2
Float
Floating Point
Frequency Phase B
SA + 300142
2
Float
Floating Point
Frequency Phase C
SA + 300144
2
Float
Floating Point
Frequency Maximum
SA + 300146
2
Float
Floating Point
[3x] Input Register, Unit : Register(16 Bits)
Power Meter Type
PM_SA + 300000
1
Int16
3133
Reserved
PM_SA + 300001
1
-
Reserved
Reserved
PM_SA + 300002
1
-
Reserved
Firmware Version
PM_SA + 300003
1
BCD
0x0100~
Address / NetID
PM_SA + 300004
1
UInt16 1~247
Error Code
PM_SA + 300005
1
UInt16
-1=Initializing
0=Failed
1=Success
IP1
PM_SA + 300006
1
Int16
0~255
IP2
PM_SA + 300007
1
Int16
0~255
IP3
PM_SA + 300008
1
Int16
0~255
IP4
PM_SA + 300009
1
Int16
0~255
Port Number
PM_SA + 300010
1
UInt16 1~65535
Reserved
PM_SA + 300011
1
-
Reserved
PT Ratio
PM_SA + 300012
2
Float
0.01~655.35
CT Ratio
PM_SA + 300014
2
Float
1~65535