ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
246
DI Ch.1
100201
1
Byte
0=OFF, 1=ON
DI Ch.2
100202
1
Byte
0=OFF, 1=ON
DI Ch.3
100203
1
Byte
0=OFF, 1=ON
Input Register (3x), Unit : Register(16 Bits)
AI Ch.0
300200
2
Float
Floating Point
AI Ch.1
300202
2
Float
Floating Point
AI Ch.2
300204
2
Float
Floating Point
AI Ch.3
300206
2
Float
Floating Point
DI Counter 0
300208
2
UInt32 0~4294967295
DI Counter 1
300210
2
UInt32 0~4294967295
DI Counter 2
300212
2
UInt32 0~4294967295
DI Counter 3
300214
2
UInt32 0~4294967295
Holding Register (4x), Unit : Register(16 Bits)
AO Ch.0
400200
2
Float
Floating Point
AO Ch.1
400202
2
Float
Floating Point
(6) PUE Data
This block stores information of 10 user-defined PUEs.
Parameter Name
Modbus
Address
Length
Data
Type
Range
[3x] Input Register, Unit : Register(16 Bits)
PUE 1
300300
2
Float
Floating Point
PUE 2
300302
2
Float
Floating Point
PUE 3
300304
2
Float
Floating Point
PUE 4
300306
2
Float
Floating Point
PUE 5
300308
2
Float
Floating Point
PUE 6
300310
2
Float
Floating Point
PUE 7
300312
2
Float
Floating Point
PUE 8
300314
2
Float
Floating Point
PUE 9
300316
2
Float
Floating Point
PUE 10
300318
2
Float
Floating Point
Summary of Contents for PMC-523 Series
Page 1: ...ICP DAS PMC 523x PMC 224x PMD Power Meter Concentrator Series User Manual Version 3 2 4...
Page 165: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 150 Figure9 14 The Import of MQTT Topic...
Page 205: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 190 Figure10 53 PUE Setting Page 2...