ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
162
name of the SNMP Trap in the “Nickname” field and you could also
input the description of this SNMP Trap in the “Description” field.
iv
Input the Specific ID value of the SNMP Trap in the “Specific ID”
field.
v
Click on “Add new variable bindings” to add a new variable binding
for the SNMP Trap.
vi
After clicking the “Add new variable bindings”, the Variable Binding
Setting Page will appear. Select the variable type first. PMC/PMD
provides two variable types as “Channel Data” and “User-Defined
Data” for selection. If you select the variable type as “Channel Data”
type, The setting page interface will be shown as below:
Figure10-14 :
“Channel Data”Type Setting Page
Based on the “Channel Data” type interface, it provides the encoded
string for user to easily add one real-time power data or I/O channel
data as the variable binding in SNMP Trap each time. Select the
“Source”, “Module”, “Channel” and “Format” from the dropdown list,
and click the “OK” button to add the power data or I/O channel to the
variable bindings list of the SNMP Trap.
The following figure shows two variable binding examples in “Channel
Data” type are included in the SNMP Trap. The first variable binding is
the voltage value of PM-3114 Loop 1 on the module 1 that is connected
to COM2. The second variable binding is the kW value of PM-3114
Loop 1 on the module 1 that is connected to COM2.