ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
238
Mobile Network Signal
Strength
300032
1
Int16
-32768~32767(dbm)
Mobile Network Signal
Strength (Percent)
300033
1
Int16
0, 20, 40, 60, 80, 100
micro SD Free Space
300034
1
UInt16 0~65535(MB)
FTP Upload Status
300035
1
Int16
-1=Initializing
0=Failed
1=Success
Contract Capacity
300036
2
Float
0~99999999(kW)
Carbon Footprint Factor
300038
2
Float
0.001~99999999
Calculation Interval for
Demand
300040
1
UInt16 15/30/60(minutes)
(2) RS-485-1 / RS-485-2 / LAN Modules Connection Status
This block stores the connection status of M-7000/DL/IR, power meter and Modbus
TCP/RTU modules that are connected to the PMC/PMD, detailed information is
shown as below:
Parameter Name
Modbus
Address
Length
Data
Type
Range
[1x] Discrete Input, Unit : Coil (8 Bits)
The connection status of
M-7000/DL/IR, power meter
and Modbus RTU modules
that are connected to
RS-485-1.
100060-
100075
1
Byte
0=Offline
1=Online
The connection status of
M-7000/DL/IR, power meter
and Modbus RTU modules
that are connected to
RS-485-2.
100076-
100091
1
Byte
0=Offline
1=Online
The connection status of
power meter and Modbus
TCP modules that are
connected to LAN.
100092-
100107
1
Byte
0=Offline
1=Online
(3) RS-485-1 / RS-485-2 / LAN Modules Information
This block stores the module type or address information of M-7000/DL/IR, power
Summary of Contents for PMC-523 Series
Page 1: ...ICP DAS PMC 523x PMC 224x PMD Power Meter Concentrator Series User Manual Version 3 2 4...
Page 165: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 150 Figure9 14 The Import of MQTT Topic...
Page 205: ...ICP DAS PMC 523x PMC 224x PMD Series User Manual 190 Figure10 53 PUE Setting Page 2...