ICP DAS PMC-523x/PMC-224x/PMD Series User Manual
250
M-7016 (1 DI
、
4 DO
、
2 AI
、
1 AO channel)
Parameter Name
Modbus Address Length
Data
Type
Range
[0x] Coils Output, Unit : Coil(8 Bits)
DO Ch.0
SA + 000000
1
Byte
0=OFF, 1=ON
DO Ch.1
SA + 000001
1
Byte
0=OFF, 1=ON
DO Ch.2
SA + 000002
1
Byte
0=OFF, 1=ON
DO Ch.3
SA + 000003
1
Byte
0=OFF, 1=ON
[1x] Discrete Input, Unit : Coil (8 Bits)
DI Ch.0
SA + 100000
1
Byte
0=OFF, 1=ON
[3x] Input Register, Unit : Register(16 Bits)
AI Ch.0
SA + 300000
2
Float
Floating Point
AI Ch.1
SA + 300002
2
Float
Floating Point
DI Counter 0
SA + 300004
1
UInt16 0~65535
[4x] Holding Register, Unit : Register(16 Bits)
AO Ch.0
SA + 400000
2
Float
Floating Point
M-7017
、
M-7017R
、
M-7017C
、
M-7017RC
、
M-7017R-A5
、
M-7018
、
M-7018R
、
M-7019R (8 AI channel)
Parameter Name
Modbus Address Length
Data
Type
Range
[3x] Input Register, Unit : Register(16 Bits)
AI Ch.0
SA + 300000
2
Float
Floating Point
AI Ch.1
SA + 300002
2
Float
Floating Point
AI Ch.2
SA + 300004
2
Float
Floating Point
AI Ch.3
SA + 300006
2
Float
Floating Point
AI Ch.4
SA + 300008
2
Float
Floating Point
AI Ch.5
SA + 300010
2
Float
Floating Point
AI Ch.6
SA + 300012
2
Float
Floating Point
AI Ch.7
SA + 300014
2
Float
Floating Point