2.
Place the bracket over the power supply inlets on the right rear of the 2145 UPS-1U, so that the two
screw holes line up.
3.
Ensure that the power cable runs through the rightmost slot in the bracket.
4.
Secure the bracket in place with one screw on each side, as shown in Figure 297.
Removing the 2145 UPS-1U
Before you remove the 2145 UPS-1U, read all safety notices.
Use the reference numbers in parentheses at the end of each notice, such as (C003) for example, to find
the matching translated notice in
IBM Systems Safety Notices
.
DANGER
Uninterruptible power supply units contain specific hazardous materials. Observe the following
precautions if your product contains an uninterruptible power supply:
v
The uninterruptible power supply contains lethal voltages. All repairs and service must be
performed only by an authorized service support representative. There are no user serviceable
parts inside the uninterruptible power supply.
v
The uninterruptible power supply contains its own energy source (batteries). The output
receptacles might carry live voltage even when the uninterruptible power supply is not connected
to an ac supply.
v
Do not remove or unplug the input cord when the uninterruptible power supply is turned on.
This removes the safety ground from the uninterruptible power supply and the equipment
connected to the uninterruptible power supply.
v
The uninterruptible power supply is heavy because of the electronics and batteries that are
required. To avoid injury, observe the following precautions:
– Do not attempt to lift the uninterruptible power supply by yourself. Ask another service
representative for assistance.
– Remove the battery, electronics assembly, or both from the uninterruptible power supply
before removing the uninterruptible power supply from the shipping carton or installing or
removing the uninterruptible power supply in the rack.
(D007)
CAUTION:
This part or unit is heavy but has a weight smaller than 18 kg (39.7 lb). Use care when lifting,
removing, or installing this part or unit. (C008)
Perform the following steps to remove the 2145 UPS-1U:
svc00200
Figure 297. 2145 UPS-1U power cable-retention bracket
272
IBM SAN Volume Controller Hardware Maintenance Guide
Summary of Contents for SAN Volume Controller
Page 2: ......
Page 14: ...xii IBM SAN Volume Controller Hardware Maintenance Guide...
Page 22: ...xx IBM SAN Volume Controller Hardware Maintenance Guide...
Page 26: ...xxiv IBM SAN Volume Controller Hardware Maintenance Guide...
Page 316: ...290 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 322: ...Taiwan Class A compliance statement 296 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 324: ...298 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 326: ...300 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 332: ...306 IBM SAN Volume Controller Hardware Maintenance Guide...
Page 333: ......
Page 334: ...Part Number 31P1173 Printed in USA GC27 2226 03 1P P N 31P1173...