POWeR SUPPly SeTUP
powermax
65/85
Operator Manual
2-13
engine-driven generator recommendations
Generators used with the Powermax65 or Powermax85 should satisfy the following requirements:
CSA
• 1-phase, 50/60 Hz, 230/240 VAC
• 3-phase, 50/60 Hz, 200-600 VAC (480 VAC recommended for best performance)
Ce
• 3-phase, 50/60 Hz, 380/400 VAC (400 VAC recommended for best performance)
engine drive
rating
System output
current
Performance
(arc stretch)
20 kw
85 A
Full
15 kw
70 A
Limited
15 kw
65 A
Full
12 kw
65 A
Limited
12 kw
40 A
Full
8 kw
40 A
Limited
8 kw
30 A
Full
ote:
N
Based on the generator rating, age, and condition, adjust the cutting current as
needed.
If a fault occurs while using a generator, turning the power switch quickly to OFF and
then to ON again (sometimes called a “quick reset”) may not clear the fault. Instead,
turn OFF the power supply and wait 30 to 45 seconds before turning ON again.