UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
4 User Interface
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
125
Figure 4-31
Advanced parameters
Item
Description
Default Value Value Range
Current source
Specifications of the Hall effect
sensor used to detect iBOX
current.
200 A
Hall 200A, Hall
600A, Hall
1500A
Batt. abnormal
BCB trip
Whether the BCB trips when
batteries are abnormal.
Disable
Disable, Enable
Multi-Hall cur.
setting
Multi-Hall cur. setting
is equal
to the number of Hall effect
sensors at the positive or negative
terminal of a battery string
(Multi-Hall cur. setting ≥ 1).
1
1–8
Figure 4-32
Battery string configuration
Set the iBOX and iBAT number for each battery string.
Dry Contact Settings