UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
4 User Interface
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
137
Number
Area
Function
3
Information
area
Displays system monitoring information.
The parameters that have been introduced in the LCD section are not described in the WebUI
section.
The information displayed in
Active Alarms
and
Real-time Data
is the same as that on the
LCD, so the information is not described in the WebUI section.
4.2.2.1 Parameter Settings
Figure 4-47
Parameter settings
System Settings
Item
Description
Default Value Value Range
High ambient
temperature
alarm threshold
(°C)
An alarm is generated when the
ambient temperature reaches or
exceeds the threshold specified
by this parameter.
55
40–60
Low ambient
temperature
alarm threshold
(°C)
An alarm is generated when the
ambient temperature is lower
than the threshold specified by
this parameter.
–10
–20 to 0
EPO detection
Indicates whether to enable
emergency power-off (EPO).
EPO is performed only when this
parameter is enabled and the
EPO switch is triggered.
When
EPO detection
is changed
from
Disable
to
Enable
, check
that the EPO cable is connected
correctly.
Disable
Disable, Enable
Bus capa. life
If this parameter is set to
Enable
,
the UPS detects the bus capacitor
lifespan.
Disable
Disable, Enable