4 User Interface
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
129
Figure 4-35
Maintenance 1
Figure 4-36
Maintenance 2
On the
System Info
>
Settings
>
iBOX Settings
>
Basic Param.
screen, if the
Number of iBOXs
is not
0
the
Maintenance
is displayed on the
iBOX Control
screen.
Choose
Monitoring
>
Param. Settings
>
System Settings
on the WebUI, if the
Bus capa. life
is set
to
Enable
, the
Maintenance
is displayed on the
Bus Capa. Life
screen.
Battery Maintenance
Perform battery maintenance when no alarm is active on the UPS. Otherwise, the UPS
may supply no power.
A proportion of battery capacity will discharge during battery maintenance. This reduces
the discharge time before the next charge.
Do not perform battery maintenance when a D.G. is connected.
Perform battery maintenance periodically to increase the battery lifespan and improve the
UPS reliability. Battery maintenance includes
Forced Equalized Charging
,
Shallow Dis.