UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
5 Operations
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
175
In ECO mode, the bypass takes priority over the inverter in supplying power. If the
bypass is disconnected, the UPS transfers to normal mode.
Both a single UPS and the parallel system support the ECO mode for higher efficiency.
To avoid frequent transfer between ECO mode and normal mode, do not set the ECO
mode when the bypass input is unstable or is sensitive to load changes.
ECO mode is not recommended when the load is less than 10%.
Before transferring the UPS to ECO mode, ensure that the bypass module works
properly.
Procedure
Step 1
On the LCD, set
System Info
>
Settings
>
System Settings > Working mode
to
ECO
. The
information indicating that the UPS works in ECO mode is displayed on the LCD.
Step 2
Set the ECO voltage range.
Figure 5-13
ECO parameters
Step 3
(Optional) If you set ECO mode in bypass mode, manually start the UPS inverter.
After the inverter starts, the UPS still works in bypass mode and the inverter is on standby. If
the bypass is not normal, the inverter supplies power immediately. If the inverter is not started,
the UPS may be disconnected.