UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
4 User Interface
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
131
Figure 4-39
USB operations 2
Starting or Shutting Down the Inverter
Item
Description
Inv. ON
The
Inv. ON
screen allows you to start the inverter
manually.
Inv. OFF
The
Inv. OFF
screen allows you to shut down the
inverter manually.
ECM Switchover
Only professional personnel are allowed to use this function.
Clear faults before performing ECM active/standby switchover.
After an ECM is inserted, active and standby switchover is supported only after the ECM
is configured and starts working properly (about 30 seconds).
If the ECM to be maintained is still working, perform ECM active/standby switchover on this
screen (a dialog box is displayed for you to confirm this operation). After performing
active/standby switchover, ensure that this ECM is in standby state (that is, the green indicator
is blinking) and then maintain the ECM.
Bus Capacitor Life Forecast
If the service life of a capacitor is about to end, that is,
Module X bus capacitor life (y)
is
less than 1.0, contact Huawei technical support to replace the power module.
Wizard-based Startup
The wizard-based startup can be used to test the bypass, mains inverter, inverter/bypass
switch, battery inverter, battery charging capability, battery switch tripping and so on.