UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
C Alarm List
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
209
Alarm ID
(Alarm
ID-Cause
ID)
Alarm Name
Severity
Cause
Solution
The air channel
for the power
module is
obstructed.
functioning properly. Replace
the power module if the fans
are faulty.
0043-1
Fan abnormal
Critical
The fan for the
power module is
abnormal.
The fan
monitoring cable
for the power
module is not
working
properly.
Replace the faulty power module.
0043-2
The fan is faulty.
Check the fan or replace the
bypass module.
0043-3
The fan is faulty.
The fan
monitoring cable
is faulty.
1.
Replace the fan.
2.
Check the fan monitoring
cable.
0043-4
0047-1
Not ready
Critical
The ready switch is
OFF.
Close the ready switch.
0060-4
Inverter abnormal
Critical
A load
short-circuit
occurs.
A short circuit
occurs inside the
module. (This
fault seldom
occurs.)
The output is
incorrectly
grounded.
1.
Check load cable distributions.
2.
Check whether the output is
grounded.
3.
If the load cable connections
are normal and the output is
correctly grounded, replace the
power unit or module.
0061-2
Inverter alarm
Minor
The I2C bus is
not normal.
The E2PROM is
faulty.
1.
Rectify the fault and check
whether the alarm is cleared.
2.
If the alarm is generated again,
replace the power module.
0061-7
Inverter alarm
Minor
The bypass
waveform is not
normal.
If not all modules generate the
alarm, start the UPS, transfer it
to normal mode, and replace
the faulty module.
If all modules generate the
alarm, open the bypass input
circuit breaker. After the