UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
4 User Interface
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
118
Input Settings
Figure 4-23
Input settings
Item
Description
Default Value Value Range
D.G. mode
Set this parameter to
Enable
when a D.G. connects to the
input PDC. The UPS enters the
D.G. mode when a D.G. is
detected over dry contacts.
Disable
Disable, Enable
D.G. power
limiting (kVA)
Set these two parameters to
control the valid input current
and limiting input current, which
prevents load impact and
facilitates better cooperation
between the UPS and the D.G.
Depends on the
actual model.
0 kVA to 5000
kVA
D.G. charger
power ratio (%)
0
0%–100%
Input cur.
limiting
Specifies whether to enable or
disable input current limiting to
protect generators.
Disable
Disable, Enable
Input cur.
limiting ratio
(%)
Limits the input current to protect
the D.G.
200%
50%–200%