UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
4 User Interface
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
121
Item
Description
Default Value Value Range
frequency
range (Hz)
bypass input frequency and the
rated frequency is greater than
the specified value, the system
determines that the bypass
frequency is abnormal, so the
bypass is unavailable.
Hz
Battery Settings
Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge
time. When you set battery parameters, note the following:
Battery string sharing
is unavailable when
Single/Parallel
is set as
Single
.
Battery string sharing
affects the actual charge current and the estimated discharge time.
An incorrect setting will cause a high or low charge current, which may damage the
batteries. An incorrect estimated discharge time may cause a data backup fault.
When you set parameters, ensure the following:
Dis. cur. 0.1C EOD
≥
Dis. cur. 0.3C
EOD
≥
Dis. cur. 0.5C EOD
≥
Dis. cur. 1.0C EOD
.
A cell consists of electrodes and electrolyte, which is the basic unit for the battery. Each
cell has a nominal voltage of 2 V. A battery is a module consisting of single or multiple
cells in a shell. Each battery has a nominal voltage of 2 V, 6 V, or 12 V.
Figure 4-26
Battery settings 1