UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
3 Installation
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
70
Route cables through holes, remove the power cable cover, spare power cable cover and
battery cable cover and drill holes. After you drill holes, paste grommet strip to the hole
edge to protect cables. Reinstall the covers on the cabinet.
This section introduces the dual mains scenario. If single mains is used, you do not need to
remove the copper bars between the mains and bypass input terminals or connect the
bypass input cable.
The figures are for reference only. For more information about the recommended cable
cross-sectional area and quantity, refer to
requirements.
Figure 3-24
Power distribution module (400 kVA UPS, 500 kVA UPS)
(1) Mains input
terminal
(2) Battery input
terminal
(3) Output terminal
(4) Bypass input
terminal