UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
4 User Interface
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
116
Item
Description
Default Value Value Range
Single/Parallel
Specifies whether the UPS works
in single mode or parallel mode.
Single
Single, Parallel
Requisite
modules
Matches the system capacity.
N/A
N/A
Redundant
modules
Set this parameter based on load
capacity and redundancy
requirements.
0
0–19
Working mode
UPS working mode
Normal mode
Normal mode,
ECO, Self-load
mode, Converter
mode
ECO voltage
range
In ECO mode, when the
difference between the bypass
voltage and the rated voltage is
greater than this value, the
system determines that the ECO
voltage is abnormal and transfers
to normal mode.
±5%
±5%, ±6%, ±7%,
±8%, ±9%,
±10%
BSC mode
Set this parameter to
Standard BSC
for a dual-bus
system.
After setting this parameter to
Standard BSC
, you need to
set the two UPS systems in
the dual-bus system to
BSC
master system
and
BSC
slave system
respectively in
the
BSC master/slave system
setting. (The two UPS
systems cannot be BSC
master systems or BSC slave
systems at the same time. If
you need to change the
settings in the future, perform
operations under the guidance
of maintenance engineers.)
Non-BSC
Non-BSC,
Standard BSC
Altitude (m)
Set this parameter based on the
altitude of the place where the
rack is used.
≤ 1000
≤ 1000,
1000–2000,
2000–3000,
3000–4000,
4000–5000
Top outlet fan
N/A
Disable
Disable, Enable
Air filter
maintenance
period (d)
Specifies the rack air filter
maintenance interval. If it is set
to
0
, there is no reminder.
0
0–365
Intra-rack
These two parameters enable the
The default
0.5–120.0