UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
4 User Interface
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
147
Figure 4-53
Site configuration
The NTP parameters are used to set the NTP server address, port number, and
synchronization interval.
The default SNMP version is SNMPv3, and the preset MD5/SHA password is
Changeme1
, and the preset DES/AES password is
Changeme2
. Change the password
after your first login, preventing unauthorized access.
The standard protocols SNMP V1 and SNMP V2 have security risks. You are advised to use the
secure protocol SNMP V3.
The standard encryption algorithms MD5 and DES have security risks. You are advised to use the
secure encryption algorithms SHA and AES.
To obtain the MIB file, choose
Config.
>
Site Config.
>
SNMP
>
Download
HUAWEI_UPS_MIB
.
The
SNMP Trap
is used to set the IP address of a server on which the NMS software is
installed. The trap port needs to be the same as that on the NMS. If
SNMP Trap
is
incorrectly set or not set, system information will be lost or not reported in time.
The certificate is used for Secure Sockets Layer (SSL) encryption protection for WebUI
login. You need to apply to a third-party institution for the certificate.
Configuration Management
is used to upload and export configuration parameters in
the monitoring system.
Multi-brand Management
is used to import the brand information of a partner to the
corresponding WebUI.
Specify
Email server IP address
,
Sender's email
, and
User account authentication
required
when sending a mail and click
Test
to check whether the test email can be
received.
Configure Alarm Notification Server
is used to configure a server for
receiving alarm emails from the monitoring system.